DT-8921

HVAC Superheat and Subcooling Analyzer
Measures suction line or liquid line pressure and line temperature to calculate and display superheat and subcooling for A/C.
R-22 or R-410A
Digital LCD display in ºF/ºC
Digital LCD displays pressure in PSI/kPa


Size(HxWxD): 212mm x 78mm x 51mm

Weight: 338g

Specifications

Temperature

Range (temperature): -40ºC to 204ºC/-40ºF to 400ºF;

Resolutions: 0.1º;

Sensor type: Dual k-type thermocouple input;

Accuracy:±1ºC/±1.8ºF;

Pressure and vacuum

Working range (pressure):0 to 500 psi; 0 to 4000 kPa

Resolutions: 0.1psi or kPa, 0.1”Hg or cmHg vac.

Accuracy: ±1 psi/±6.9 kPa;

Sensor breakdown pressure: 800psi (5500 kPa)

Superheat:

Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC

Resolutions: 0.1º;

Accuracy: ±1ºC/±1.8ºF;

Subcooling:

Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC

Resolutions: 0.1º;

Accuracy: ±1ºC/±1.8ºF;








Accessories : Li battery, K-type thermocouple, Gift box .

DT-8921
>
Related downloads

Related products

  • DT-3890/3890A/3890B

  • DT-8890/8890A/8890B/8890C

  • DT-15

  • DT-8890D/8890E/8890F/8890G

  • DT-8920/8920B

  • DT-8897/8897H

  • DT-72DP

  • DT-73P

<>